Fair Isle panorama from Buness
FAIR ISLE

Thursday March 18, 2010

Home
Up
 
 

 

Fair Isle Renewable Energy Electricity System

Summary of the data for April 1999

60kW Turbine

100kW Turbine

Hours

%

Hours

%

Hours in month

720

720

Hours available (brake off)

699

97.1

714

99.2

Hours generating

654

90.8

659

91.5

Hours feeding service

557

77.4

458

63.6

Hours in synchronisation

440

Energy produced kWh

18,112

27,538

Energy utilised kWh

14,808

22,141

Energy dumped kWh

3,304

5,397

Load factor

41.93

38.25

Hours of service (all sources)

652

90.6

Hours of service (diesel)

193

26.8

Energy provided by diesels kWh

2,626

6.6

Current guaranteed supply

480

Hours diesel generation replaced by wind

287

Service hours extended by wind energy

172

Utilisation of wind energy

80.9

April has had fewer generating winds than in previous months with more periods of calm but has again been a relatively good month with a total of 68 hours in the month where there was no service supply. Utilisation of the wind energy produced was again high mainly due to continuing poor weather conditions for the time of year. The 60kW turbine was out of service for 21.3 hrs. in the month mainly due to low air. The 100kW turbine was out of service for 4.5 hrs. in the month.


Text and photographs 2008 Dave Wheeler except where otherwise credited. (Logo picture courtesy of Sumburgh SAR)
If you would like to use photographs from this site please contact dave.wheeler@fairisle.org.uk
Further images of Fair Isle are available.  Photographic commissions undertaken, websites authored. 
With over
40,000 visitors to the website each month why not advertise your Fair Isle product or service here?