Fair Isle Renewable Energy Electricity System
Summary
of the data for May 1999 |
60kW Turbine |
100kW Turbine |
|
Hours |
% |
Hours |
% |
Hours
in month |
744 |
|
744 |
|
Hours
available (brake off) |
686 |
92.2 |
742 |
99.7 |
Hours
generating |
575 |
77.3 |
582 |
78.2 |
Hours
feeding service |
441 |
59.3 |
460 |
61.8 |
Hours
in synchronisation |
440 |
|
440 |
|
|
|
|
|
|
Energy
produced kWh |
17,878 |
|
27,223 |
|
Energy
utilised kWh |
13,871 |
|
20,568 |
|
Energy
dumped kWh |
4,007 |
|
6,655 |
|
|
|
|
|
|
Load
factor |
|
40.05 |
|
36.59 |
|
|
|
|
|
Hours
of service (all sources) |
662 |
88.98 |
|
|
Hours
of service (diesel) |
200 |
26.88 |
|
|
Energy
provided by diesels kWh |
2,704 |
7.85 |
|
|
|
|
|
|
|
Current
guaranteed supply |
434 |
58.33 |
|
|
Hours
diesel generation replaced by wind |
234 |
|
|
|
Service
hours extended by wind energy |
228 |
|
|
|
Utilisation
of wind energy |
|
76.36 |
|
|
May was a relatively calm month during which the 60kW did not
generate for 111 available hours and the 100kWdid not generate for 160 available hours.
The 60 kW turbine was out of service for a total of 45.25hrs. 30 of which was due to a
compressor trip, fortunately during this period there was no wind and virtually no service
was lost. The 100kW turbine was out of service for 8.25 hours in the month.
|